Calibration: |
Single element
thermocouple type 'K' according to ANSI MC96.1 |
Connection: |
compensated
male connector with body in moulded nylon and M8X1 metal thread to
DIN-VDE0627 Degree of protection IP-67 Temperature MAX 90C |
Type of construction: |
With densely
packed magnesium oxide insulation and ungrounded hot junction |
Insulation
Resistance: |
100 M ohm with a
500 Vd.c |
Temperature limit: |
1150°C for
thermocouple type K |
Sheath material: |
INCONEL 600 for
thermocouple type K |
Process connection: |
1/4" gas cil.
fitting with bayonet lock cap for %%c2 probe with spring and spring stop |